Belangrikste tegniese parameters
| Model | CKG3-7.2/160-630-4 | |||
| Hoofstroombaan-gegradeerde spanning (KV) | 7.2 | 7.2 | 7.2 | 7.2 |
| Hoofstroombaan-gegradeerde stroom (A) | 160 | 250 | 400 | 630 |
| Hoofstroombaanmaakvermoë (A/100 Ops.) | 1600 | 2500 | 4000 | 6300 |
| Hoofstroombaanbrekingsvermoë (A/25 Ops.) | 1280 | 2000 | 3200 | 5000 |
| Maksimum breekvermoë (A/3 Ops.) | 3200 | 3200 | 4000 | 6300 |
| Meganiese lewensduur (Operasies) | 1000000 | 1000000 | 1000000 | 1000000 |
| Kragfrekwensie-weerstandspanning vir hoofstroombaan (kV) | 32 | 32 | 32 | 32 |
| Kragfrekwensie-weerstandspanning vir hulpstroombaan (kV) | 2.5 | 2.5 | 2.5 | 2.5 |
| Kragfrekwensie-weerstandspanning vir beheerkring (kV) | 2 | 2 | 2 | 2 |
| Gegradeerde bedryfsfrekwensie (Ops./h) | 300 | 300 | 300 | 300 |
| Oopmaaktyd (ms) | ≤120 | ≤120 | ≤120 | ≤120 |
| Sluitingstyd (ms) | ≤150 | ≤150 | ≤150 | ≤150 |
| Klaring tussen oop kontak (mm) | 4 ±0.5 | 4 ±0.5 | 4 ±0.5 | 4 ±0.5 |
| Oor reis (mm) | ≥1.2 | ≥1.2 | ≥1.2 | ≥1.2 |
Oorsig en installasie dimensies